AHI Carrier Catalog | Page 340

(1) DIMENSIONS (L),(W),(H),ARE FOR STANDARD MACHINE. THE DIMENSIONS ARE CHANGED BY PARTS ADDED. (2) (3) (4) INDICATES THE POSITION OF ANCHOR BOLTS. CLEARANCE SPACE MUST BE SAVED EITHER SIDE OF THE CHILLER MATING FLANGE OF ALL EXTERNAL WATER PIPING ARE PROVIDE WELDED ANSI 150LB FLANGE WITH CHILLER. (5) INDICATES THE POSITION OF THE POWER SUPPLY CONNECTION ON CONTROL PANEL.(DIA. 35 MM) (6) INSTALLATION CLEARANCE ¥LONGITUDINAL DISTANCE:1000 MM ¥TOP :200 MM ¥OTHERS:500 MM Wire connection OD 35 hole 270 CHW inlet 6 inch 65 0 0 60 0 4500 R Tube removal 4940(L) 2545 2365 2495 1660 1550 1476 Rupture Disk 2 inch 2500 Drain outlet 2 inch 2610(H) CHW outlet 6 inch 4164 1022 1630(W) Steam inlet 8 inch COW outlet 8 inch 3836 3315 1075 1100 225 1066 ¥ • £ • 815 COW inlet 8 inch 611 250 0 CHW in/out COW inlet 4329 4105 Drain outlet 0 275 270 0 Steam inlet 0 335 1156 1170 260 0 COW outlet 4164 3836 3315 1075 0 380 16TJ 41 through 16TJ 42 1150 1110 Wire connection OD 35 hole 275 50 0 0 240 60 0 4500 R Tube removal 4990(L) 1700(W) COW outlet 10 inch CHW outlet 8 inch CHW inlet 8 inch 2805 2780 2755 2595 Rupture Disk 2 inch 1810 1612 Drain outlet 2-1/2 inch 1550 1142 2860(H) Steam inlet 8 inch ¥ • £ • 820 COW inlet 10 inch 577 250 0 0 Drain outlet COW inlet CHW in/out 4335 4105 0 301 269 350 0 1221 Steam inlet 275 0 1255 COOLING NOTES 0 380 16TJ 31 through 16TJ 32 COW outlet Note: Dimensions are for guidance only. Always refer to the certified drawings supplied upon request when designing an installation. 340 C A R R I E R 2 0 1 6 / 2 0 1 7