AHI Carrier Catalog | Page 337

SINGLE-EFFECT STEAM-FIRED ABSORPTION CHILLERS 16TJ 11-53 Fast digital PID control Graph 5 - Steam valve opening control Variable (5-30 minutes) The introduction of new digital PID control stabilises the chilled water temperature with high accuracy. It quickly responds to the load fluctuation and supplies stable chilled water temperature. It is suitable for air-conditioning intelligent buildings which require sophisticated control. Example: 15 minutes 30 minutes Balancing the load and flow rate with the absorbent pump’s inverter control enables efficient and energy-saving operation. As a result, it reduces input energy and electric power consumption. Running cost is decreased by 5% compared to non-inverter control. Steam control valve opening ratio Cooling water entering temp. Chilled water entering temp. Setting 7 °C Chilled water leaving temp. COOLING Temperature (°C) Saving energy with the inverter (option) Steam consumption (%) Steam control opening ratio (%) Steam consumption Graph 4 - Running cost curve Time (minutes) 100 ■■ This ensures quick response to rapid changes and maintains stable operation. ■■ The safe operating zone is between 19 °C and 34 °C cooling water temperature (for a nominal cooling water entering temperature of 32 °C). 80 Non-inverter control 60 40 100 20 40 60 80 100 Cooling load factor (%) Notes: 1. Chilled-water leaving temperature 7 °C constant 2. Cooling water entering temperature: Maximum input (%) 20 0 HEATING HEATING Graph 6 - Safe operating zone chart Inverter control 80 60 40 20 0 H--13 H--4 Load factor (%) Temperature (°C) 100 32 Cooling water entering temperature (°C) 50 27 H = 32 °C (variable from 20 °C to 33 °C) 30 25 H H+2 Crystallisation protection Purge system ■■ The high-performance purge system maintains the required operating pressure, preserves chiller performance characteristics, minimises chiller maintenance to one purge operation per season (for yearround operation). ■■ A microprocessor monitors the absorbent concentration. Steam supply is stopped, and the unit is returned to normal operation, when the concentration is over a certain limit, to prevent the crystallisation of absorbent. AIR TREATMENT Energy consumption ratio (%) Expansion of safe operating zone Steam valve opening control C A R R I E R 2 0 1 6 / 2 0 1 7 CONTROLS ■■ At the start-up, the opening angle of the steam control valve is controlled in three stages, reducing the amount of steam and the time needed to reach the desired level, compared with the previous model. ■■ Adjusting the opening speed of the steam control valve at the second and third stage, it is possible to set up the most suitable conditions for the site auxiliary equipment. 337