Standard
Option
400 V - 3 phase - 50Hz
(Voltage control within ±10%, frequency control within ±5%)
Contact the Carrier representative
One section
Multi-shipment
Refrigerant temperature
Chilled water freeze protection
Chilled water flow switch
Cooling water temperature
HT generator temperature
HT generator pressure
HT generator solution level
Crystallisation protection
Motor protection
Cooling water flow switch
Capacity control
Digital PID control by chilled-water temperature
Inverter control of #1 absorbent pump
Parts
Selected by Carrier
No option
Painting
Munsell 5Y-7/1
No option
Indication lights
Operation
Stop
Alarm
No option
No option
No option
Display
LED
No option
External terminals
(volt-free normally open contact)
Operation indication
Stop indication
Alarm indication
Feedback indication
Cooling mode indication
No option
Structure
Parts
Indoor type
Selected by Carrier
No option
No option
Wire: 600 V polyvinyl grade (chloride-insulated wires)
Pipe: Plicatube (flexible metal conduits)
No option
No option
Indoor
5 °C through 40 °C
Relative humidity: Max. 90 % at 45 °C
No option
No option
No option
Be sure the following are not present:
- Corrosive gas
- Explosive gas
- Poisonous gas
No option
Electricity
Power supply
Shipment
Control
Safety functions
HEATING HEATING
Control panel
Electrical wiring and piping
Insulation condition
Place
Ambient temperature
Ambient humidity
Atmosphere
Features and advantages
■■ They reduce the contribution to global warming and
minimise the global impact by greatly reducing electricity
consumption and production of greenhouse gases.
■■ The solution inhibitor has no impact on the environment.
■■ An absorption chiller does not utilise mechanical moving
parts, and this leads to quiet, vibration-free operation.
■■ The use of high-efficiency heat transfer surfaces has
reduced the space required for installation of the
absorption chiller, resulting in a smaller footprint.
CONTROLS
■■ The Carrier 16TJ single-effect absorption chillers are
designed for cooling applications where low-pressure
steam is available as waste heat.
■■ They can tie into district steam systems.
■■ Carrier absorption chillers allow diversification of critical
cooling requirements. Critical cooling loads are met with
minimal electrical power input.
■■ They allow smaller emergency generators compared to
an electrical driven chiller.
■■ The units are ozone-safe and CFC-free. Cooling
requirements are met without chlorine-based refrigerants.
AIR TREATMENT
Item
COOLING
SINGLE-EFFECT STEAM-FIRED ABSORPTION CHILLERS
16TJ 11-53
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
335