AHI Carrier Catalog | Page 333
SINGLE-EFFECT STEAM-FIRED ABSORPTION CHILLERS
16TJ 11-53
Component identification
1
2
3
COOLING
4
5
7
6
Legend
9
10
1. Condenser
2. Steam inlet
3. Generator
4. Chilled-water outlet
5. Control panel
6. Evaporator
7. Chilled-water inlet
8. Cooling water inlet
9. Heat exchanger
10. Heat reclaimer
11. Absorber
HEATING HEATING
8
11
Scope of supply
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
AIR TREATMENT
2. Absorption chiller, comprising:
1. Lower shell
-- Evaporator and refrigerant dispersion tray
-- Absorber and absorbent dispersion tray with
eliminators
-- Bases.
2. Upper shell
-- Generator with eliminators
-- Condenser with eliminators
-- Rupture disk.
3. Heat exchangers with refrigerant drain heat reclaimer
4. Pumps
-- Absorbent pump with isolating valves
-- Refrigerant pump with isolating valves
-- Purge pump.
5. Purge unit
-- Purge tank with ejector device
-- Diaphram valves and piping with liquid trap
-- Pressure sensor
-- Palladium cell with heater.
6. Control panel
-- Controller with data display
-- LEDs and operation buttons
-- Inverter for absorbent pump (option)
-- Circuit breaker
-- Transformer
-- Relays and terminal blocks
-- Purge pump operation switch.
7. Locally mounted parts
-- Temperature sensors
-- Chilled-water flow switch.
8. Interconnecting piping and wiring
-- Refrigerant and absorbent piping
-- Internal power and control wiring.
9. Initial charge
-- Absorbent (lithium bromide)
-- Refrigerant (water)
-- Inhibitor (lithium molybdate).
CONTROLS
1. Standards met
The units comply with the following standards:
-- ARI 560-2000
-- 2006/42/EC (machine directive)
-- 2006/95/EC (low-voltage directive)
-- 2004/108/EC (electromagnetic compatibility directive)
-- 97/23/EC (pressure equipment directive).
333