AHI Carrier Catalog | Page 331
SINGLE-EFFECT STEAM-FIRED ABSORPTION CHILLERS
16TJ 11-53
Physical data
Single effect steam-fired absorption chillers
16TJ
Cooling capacity
kW
11
12
13
14
21
22
23
24
352
422
527
633
738
844
985
1125
Flow rate
l/s
15.1
18.2
22.7
27.3
31.7
36.4
42.5
48.3
Pressure drops
kPa
50
51
64
67
60
64
42
45
Connection (ANSI)
in
4
4
4
4
5
5
6
6
Retention volume
m3
0.12
0.13
0.15
0.17
0.22
0.25
0.29
0.31
COOLING
Chilled water system*
Cooling water system*
Flow rate
l/s
22.7
27.3
34.2
40.8
47.8
54.4
63.6
72.8
Pressure drops
kPa
34
37
32
36
32
35
65
70
Connection (ANSI)
in
5
5
5
5
6
6
8
8
Retention volume
m3
0.33
0.37
0.41
0.45
0.58
0.63
0.69
0.76
Steam system
Consumption
kg/h
780
940
1170
1410
1640
1880
2190
2500
Steam inlet (ANSI)
in
5
5
5
5
6
6
8
8
Drain outlet (ANSI)
in
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
Control valve
in
2
2
2-1/2
2-1/2
2-1/2
3
3
4
Shutoff valve
in
2
2
2-1/2
2-1/2
2-1/2
3
3
4
mm
2690
2690
3690
3690
3790
3790
4850
4850
mm
2200
2200
2200
2200
2350
2350
2370
2370
Width
mm
1400
1400
1400
1400
1560
1560
1560
1560
Tube removal space
mm
2400
2400
3400
3400
3400
3400
4500
4500
Weight
Operating weight
kg
4000
4300
5100
5400
6700
6900
7900
8300
Max shipping weight**
kg
3500
3700
4500
4700
5800
6000
6900
7200
Power supply
V-ph-Hz
400-3-50
Apparent power
kVA
4.0
4.0
4.0
4.0
5.8
5.8
5.9
5.9
Total electric current
A
6.1
6.1
6.1
6.1
8.8
8.8
8.9
8.9
Absorbent pump, power input
kW
1.1
1.1
1.1
1.1
2.2
2.2
2.2
2.2
Absorbent pump, electric current
A
2.8
2.8
2.8
2.8
5.5
5.5
5.5
5.5
Refrigerant pump, power input
kW
0.2
0.2
0.2
0.2
0.2
0.2
0.3
0.3
Refrigerant pump, electric current
A
1.3
1.3
1.3
1.3
1.3
1.3
1.4
1.4
Purge pump, power input
kW
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
Purge pump, electric current
A
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
PD cell heater
kW
0.038
0.038
0.038
0.038
0.038
0.038
0.038
0.038
Control circuit
kW
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
*
**
In accordance with ARI 560 - 2000
12.2 / 6.7 °C (fouling factor = 0.0176 m2 K/kW)
29.4 / 38.4°C (fouling factor = 0.044 m2 K/kW)
Saturated steam 100 kPa
All sizes shipped as one-piece
AIR TREATMENT
Length
Height
HEATING HEATING
Dimensions
CONTROLS
Notes: These performance data are provided to support early design activity. For selection outside ARI operating conditions contact Carrier.
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
331