AHI Carrier Catalog | Page 305

SINGLE-EFFECT HOT WATER-FIRED ABSORPTION CHILLERS 16LJ/16LJ-A Physical data 16LJ/16LJ-A LJ Size LJ-A 01 02 03 11 12 13 14 21 22 23 24 31 32 kW 83 131 166 264 316 387 475 545 633 738 844 949 1055 Flow rate l/sec 3.58 5.64 7.14 12.6 15.1 18.5 22.7 26 30.3 35.3 40.3 45.3 50.3 Pressure drop kPa 73 60 60 72.2 78.4 48.5 52.9 46.8 50.2 102 105 104 106 Connection(ANSI) inch 2 2 1/2 2 1/2 3 3 4 4 5 5 5 5 6 6 Retention volume m3 0.06 0.08 0.08 0.11 0.13 0.15 0.17 0.22 0.25 0.28 0.30 0.35 0.38 Flow rate l/sec 5.4 8.5 10.8 20.8 25 30.6 37.5 43.1 50 58.3 66.7 75 83.3 Pressure drop kPa 23 16 15 78.8 81.8 86.6 95.4 89.1 93.4 58.4 62.5 49.8 51.6 Connection(ANSI) inch 3 4 4 5 5 5 5 6 6 8 8 8 8 Retention volume m3 0.13 0.18 0.23 0.33 0.37 0.40 0.45 0.58 0.63 0.69 0.76 0.98 1.05 Flow rate l/sec 3.28 5.17 6.56 8.4 10.1 12.3 15.1 17.3 20.1 23.4 26.8 30.1 33.5 Pressure drop kPa 58 41 41 24.7 26.4 65.6 72.8 31.5 32.5 22.0 22.1 22.4 22.3 Connection(ANSI) inch 2 2 1/2 2 1/2 4 4 4 4 5 5 6 6 6 6 Retention volume m3 0.04 0.04 0.07 0.07 0.08 0.09 0.10 0.13 0.14 0.15 0.17 0.21 0.22 Rupture disk connection inch 2 2 2 2 2 2 2 2 2 2 2 2 2 Length (L) mm 1745 2450 2450 2 740 2 740 3 750 3 750 3 850 3 850 4 870 4 870 4 920 4 920 Height (H) mm 2115 2115 2115 2 330 2 330 2 330 2 330 2 480 2 480 2 480 2 480 2 775 2 775 Width (W) mm 1255 1255 1435 1 400 1 400 1 400 1 400 1 560 1 560 1 560 1 560 1 630 1 630 Tube removal mm 900 1350 1350 2 400 2 400 3 400 3 400 3 400 3 400 4 500 4 500 4 500 4 500 Operation weight kg 2070 2680 3150 4 000 4 200 5 200 5 500 6 600 6 900 8 100 8 600 10 500 11 000 Max shipping weight kg 1820 2380 2720 3 500 3 600 4 500 4 700 5 600 5 900 7 000 7 300 9 000 9 300 Shipping method u 1 1 1 1 1 1 1 1 1 1 1 1 1 Power supply V-ph-Hz 400-3-50 Apparent power kVA 3.1 3.1 3.1 5.0 5.0 5.0 6.8 6.9 6.9 6.9 6.9 10.5 10.5 Total electric current A 4.8 4.8 4.8 7.5 7.5 7.5 10.2 10.3 10.3 10.3 10.3 15.5 15.5 Absorbent pump N°1, power input kW 0.75 0.75 0.75 1.1 1.1 1.1 2.2 2.2 2.2 2.2 2.2 3.0 3.0 Absorbent pump N°1, electric current A 2.2 2.2 2.2 2.8 2.8 2.8 5.5 5.5 5.5 5.5 5.5 7.5 7.5 Absorbent pump N°2, power input kW / / / 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.4 1.5 1.5 Absorbent pump N°2, electric current A / / / 1.4 1.4 1.4 1.4 1.5 1.5 1.5 1.5 4.7 4.7 Refrigerent pump, power input kW 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 Refrigerent pump, electric current A 0.7 0.7 0.7 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 Purge pump, power input kW 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 Purge pump, electric current A 1.1 1.1 1.1 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 PD cell heater kW 0.038 0.038 0.038 0.038 0.038 0.038 0.038 0.038 0.038 0.038 0.038 0.038 0.038 Control circuit kW 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 Capacity Chilled water system* COOLING Cooling water system* Hot water system* 400-3-50 * Condition for LJ 12,2/6,7 °C ( Fouling Factor = 0.0176 m2°C/kW) 29.4/38.4°C ( Fouling Factor = 0.044 m2°C/kW) 95/86°C ( Fouling Factor = 0.0176 m2°C/kW) * Condition for LJ-A 12/7 °C ( Fouling Factor = 0.018 m2°C/kW) 29.4/36.3°C ( Fouling Factor = 0.044 m2°C/kW) 90/80°C ( Fouling Factor = 0.018 m2°C/kW) AIR TREATMENT Weight HEATING HEATING Dimmensions CONTROLS Notes : These performance data are provided to support early design activity. For selection outside ARI operating conditions, contact Carrier C A R R I E R 2 0 1 6 / 2 0 1 7 305