AHI Carrier Catalog | Page 164

Condenser leaving water temperature, °C COOLING 65 60 55 50 45 Part load operating limits (evaporator leaving water temperature = 7°C) Maximum condenser leaving water temperature, °C In part-load operation, the limitation of the condenser leaving water temperature is due to the operating range of the screw compressor. If the condenser leaving water temperature is above the limit value given in the curves on the right, the unit will automatically change over to the mode without heat recovery: 40 60 55 50 45 40 100 90 80 70 35 60 50 40 30 Unit load, % 30 25 20 0 5 10 Evaporator leaving water temperature, °C 15 Full load Part load limit, approx. 60% Minimum load limit, approx. 30% Physical data, option 50 These are the same as for the standard unit except: 30XAS heat reclaim mode 282 342 442 482 Cooling capacity* kW 278 329 428 475 Heating capacity* kW 349 411 538 599 Total power input (unit)* kW 77.7 90.2 120.6 136.0 Total energy efficiency ratio (EER) kW/kW 3.58 3.65 3.55 3.49 Total coefficient of performance (COP) kW/kW 4.49 4.56 4.46 4.40 Operating weight** kg 3260 3320 4190 4280 Refrigerant charge kg 73 78 90 95 55 68 68 Heat reclaim condenser Water volume Flooded shell-and-tube condenser l Water connection 55 Victaulic Diameter inch 4 4 4 4 Outside diameter mm 114.3 114.3 114.3 114.3 * Nominal conditions: Entering/leaving water temperature: evaporator 12°C/7°C; heat reclaim condenser: 40°C/45°C; evaporator and heat reclaim condenser fouling factor = 0 m2 K/kW. Gross performances, not in accordance with EN14511-3:2011. These performances do not take into account the correction for the proportional heating capacity and power input ­generated by the water pump to overcome the internal pressure drop in the heat exchanger. ** Weights are for guidance only 164 C A R R I E R 2 0 1 6 / 2 0 1 7