AIR-COOLED LIQUID CHILLERS 30XAS 242-482
Electrical data
30XAS
242
282
342
442
482
2 x 150
2 x 95
2 x 150
2 x 150
2 x 240
38
50
50
50
50
Power circuit
Nominal power supply
V-ph-Hz
400-3-50
Voltage range
V
360-440
Maximum supply cable section
mm
Short-circuit stability current (TN system)*
kA
2
Control circuit
A
303
388
388
587
587
Cosine Phi maximum***
0.89
0.88
0.88
0.87
0.87
Cosine Phi nominal****
0.85
0.85
0.86
0.84
0.85
COOLING
24 V via internal transformer
Start-up current**
Standard unit
Total harmonic distortion
%
0
0
0
0
0
Maximum power input†
kW
101
113
134
184
213
Nominal unit current draw****
A
141
153
174
258
278
Maximum unit current draw (Un)†
A
165
185
218
305
353
Maximum unit current draw (Un) with option 231†
A
148
167
201
284
333
Maximum current draw (Un -10%)***
A
180
198
231
324
375
0.88
0.88
0.88
0.87
0.87
Cosine Phi nominal****
0.84
0.85
0.85
0.83
0.84
kW
105
118
139
190
221
A
141
153
175
254
271
Maximum current draw (Un)
A
172
194
229
318
368
Maximum current draw (Un -10%)***
A
187
207
242
337
390
Maximum power inpu t†
Nominal current draw****
†
*
**
***
****
†
kA eff: efficiency value: rms for English version
Instantaneous start-up current (locked rotor current in star connection of the compressor).
Values obtained at operation with maximum unit power input.
Values obtained at standard Eurovent unit operating conditions: air 35°C, water 12/7°C.
Values obtained at operation with maximum unit power input. Values given on the unit name plate.
Note:
Motor and fan electrical data if the unit operates at Eurovent conditions (motor ambient temperature 50°C): 1.9 A
Start-up current: 8.4 A
Power input: 760 W
Remote management (EMM option 156)
-- User safety: this contact can be used for any
customer safety loop; opening of the contact
generates a specific alarm
-- Ice storage end: when ice storage has finished, this
input permits return to the second set-point
(unoccupied mode)
-- Time schedule override: closing of this contact
cancels the time schedule effects
-- Out of service: this signal indicates that the chiller is
completely out of service
-- Chiller capacity: this analogue output (0-10 V)
gives an immediate indication of the chiller capacity
CONTROLS
■■ The Energy Management Module offers extended remote
control possibilities:
-- Room temperature: permits set-point reset based
on the building indoor air temperature (with Carrier
thermostat)
-- Set point reset: ensures reset of the cooling set-point
based on a 4-20 mA or 0-5 V signal
-- Demand limit: permits limitation of the maximum chiller
power or current based on a 0-10 V signal
-- Demand limit 1 and 2: closing of these contacts
limits the maximum chiller power or current to two
predefined values.