AIR-COOLED LIQUID CHILLERS 30XAS 242-482
Physical data
30XAS
242
282
342
442
482
430
3.87
2.93
B
467
3.96
2.87
C
432
3.97
2.96
469
4.07
2.91
461
3.75
3.15
A
486
3.79
3.09
B
462
3.84
3.18
4.55
4.36
488
3.89
3.13
4.60
4.41
103
70
102
70
97
65
96
64
95
62
94
61
92
59
91
58
98
66
98
66
98
66
98
66
4798
2253
2297
4798
2253
2297
4798
2253
2297
4798
2253
2297
3630
3990
3950
3720
4150
4070
HEATING HEATING
AIR TREATMENT
† Eurovent-certified performances in accordance with standard EN14511-3:2013.
Cooling mode conditions: evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C. evaporator fouling factor 0 m2 K/W
†† Gross performances, not in accordance with EN14511-3:2013. These performances do not take into account the correction for the proportional heating capacity and power input
generated by the water pump to overcome the internal pressure drop in the heat exchanger. Evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C.
evaporator fouling factor
0 m2 K/W
* Options: 119 = High energy efficiency, 257 = low noise level, 279 = compressor enclosure, 258,= very low sound level, 254 = traditional coils (Cu/Al), 255 = traditional coils (Cu/Al)
without slots
** Weights are guidelines only. Refer to the unit nameplate.
*** in dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with
ISO 9614-1 and certified by Eurovent.
**** in dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated from
the sound power level Lw(A).
Notes:
1
Option 119 can be used with options 254 or 255. Contact your Carrier representative for the performances.
Eurovent certified data
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
159
CONTROLS
Air conditioning application as per EN14511-3:2013† - standard unit and unit with option 279*
Nominal cooling capacity
kW
232
284
334
ESEER
kW/kW
3.78
3.93
3.99
EER
kW/kW
2.76
3.00
3.08
Eurovent class cooling
C
B
B
Air conditioning application†† - standard unit and u nit with option 279*
Nominal cooling capacity
kW
233
285
335
ESEER
kW/kW
3.85
4.01
4.09
EER
kW/kW
2.78
3.03
3.11
Air conditioning application as per EN14511-3:2013† - unit with option 119 and unit with options 119/279
Nominal cooling capacity
kW
245
285
345
ESEER
kW/kW
3.69
3.69
3.80
EER
kW/kW
2.97
3.15
3.24
Eurovent class cooling
B
A
A
Air conditioning application†† - unit with option 119 and unit with options 119/279
Nominal cooling capacity
kW
245
286
346
ESEER
kW/kW
3.75
3.76
3.90
EER
kW/kW
2.99
3.18
3.28
IPLV - standard unit
kW/kW
4.23
4.55
4.72
IPLV - unit with option 119*
kW/kW
4.16
4.23
4.44
Sound levels - Standard unit
98
Sound power level***
dB(A)
99
98
Sound pressure level at 10 m****
dB(A)
67
66
66
Unit + option 279*
Sound power level***
dB(A)
94
94
93
Sound pressure level at 10 m****
dB(A)
62
62
61
Unit + option 257*
Sound power level***
dB(A)
92
92
91
Sound pressure level at 10 m****
dB(A)
60
60
59
Unit + option 258*
Sound power level***
dB(A)
89
89
88
Sound pressure level at 10 m****
dB(A)
57
57
56
Unit + option 119*
Sound power level***
dB(A)
96
96
96
Sound pressure level at 10 m****
dB(A)
64
64
63
Unit + option 119* + 279*
Sound power level***
dB(A)
96
96
96
Sound pressure level at 10 m****
dB(A)
64
64
63
Dimensions - standard unit
Length
mm
2410
3604
3604
Width
mm
2253
2253
2253
Height
mm
2297
2297
2297
Dimensions - Unit + options 254/255*
Length
mm
3604
3604
4798
Width
mm
2253
2253
2253
Height
mm
2297
2297
2297
Operating weight**
Standard unit
2390
2810
2870
Unit + option 119*
kg
3070
3190
Unit + option 254/255*
kg
2540
3060
3140
COOLING
Cooling