AIR-COOLED LIQUID CHILLERS WITH
INTEGRATED HYDRONIC MODULE 30RB 602-802
Operating limits
Evaporator water flow rate
Operating range - 30RB 602-802
30RB 602-802 units
30RB 602-802 units
Evaporator
Entering water temperature at start-up °C
Leaving water temperature during
°C
operation
Condenser
Outdoor ambient operating temperature
Standard unit
°C
Unit with options 28B, 28C (winter
°C
operation)
Unit with option 28 (winter operation)
°C
Available static pressure
Standard unit (outdoor installation)
Pa
Unit with option 12 (indoor installation) Pa
Minimum
6.8*
3.3
Maximum
40
15**
Minimum
Maximum
0***
-10
48
48
-20
48
0
0****
0
200
-10
-20
3.3
*
15
Leaving evaporator water temperature, °C
Notes:
Evaporator ∆T = 5 K
The evaporator is protected against frost down to -20°C.
Legend:
Standard unit operating at full load.
Operating range, units equipped with options 28, 28B, 28C “Winter operation”.
Option 28 (with variable-speed lead fan for each circuit) allows operation down to
-20°C outside temperature.
Options 28B, 28C (with two-speed lead fan for each circuit) allows operation down to
-10°C outside temperature. In addition to options 28, 28B, 28C the unit must either be
equipped with the evaporator frost protection option (for units without hydronic module
option) or the evaporator and hydronic module frost protection option (for units with
hydronic module option) or the water loop must be protected by the installer by adding
a frost protection solution.
CONTROLS
AIR TREATMENT
For application requiring operation at less than 8 or 6.8°C respectively, contact Carrier
for unit selection using the Carrier electronic catalog.
** For an application, requiring operation up to +15°C leaving water temperature, contact
Carrier for the selection of the unit.
*** For operation from 0°C to -10°C the units must be equipped with options 28B, 28C “Winter
operation”. For operation from 0°C to -20°C the units must be equipped with option 28
“Winter operation”. For both options the unit must either be equipped with the evaporator
frost protection option (for units without hydronic module option) or the evaporator and
hydronic module frost protection option (for units with hydronic module option) or the water
loop must be protected against frost by the installer, using an anti-freeze solution.
Maximum outside temperature: For tra nsport and storage of the 30RB units the minimum and maximum allowable temperatures are -20°C and +48°C. It is recommended
that these temperatures are used for transport by container.
**** Unit with fans with available pressure up to 200 Pa.
†
30RB 162 units use options 28B, 28C for outside temperatures below 10°C.
COOLING
Unit operating limits
HEATING HEATING
The maximum flow rate corresponds to a pressure loss of 100 kPa (heat exchanger
without hydronic module).
48
Option 28
*
Maximum flow rate, l/s*
50.6
50.6
50.6
50.6
Options 28B, 28C
Minimum flow rate, l/s
7.9
8.7
9.6
10.3
602
672
732
802