Operating conditions Curve No. 1 2 3 Eurovent 4 5 Nominal and maximum air flows per circuit Outside Entering water Leaving water temperature, temperature, temperature, Load % °C °C °C 25 25 35 15 10 12 10 5 7 100 100 100 45 45 15 10 10 5 100 100 Nominal/maximum air flow, l/s 30RB 602 672 732 802 Circuit A Circuit B Circuit C 13540/16670 13540/16670 18060/22220 18060/22220 13540/16670 13540/16670 18060/22220 18060/22220 13540/16670 18060/22220 13540/16670 18060/22220 COOLING Sound power level at the discharge duct outlet for all circuits 30RB Sound power level 10-12 W dB(A) 602 672 732 802 96.5 97 97.5 98 Partial heat reclaim using desuperheaters (option 49) This option permits the production of free hot water using heat reclaim by desuperheating the compressor discharge gases. The option is available for the whole 30RB range. A plate heat exchanger is installed in series with the air condenser coils on the compressor discharge line of each circuit. Physical data, 30RB units with partial heat reclaim 30RB - partial heat reclaim mode Cooling capacity* Heating capacity* Unit power input* Energy efficiency ratio* Operating weight** Standard unit*** Unit with options**** Unit with options† Desuperheater in circuits A/B/C Water volume circuit A Water volume circuit B Water volume circuit C Max. water-side operating pressure Water connections Connection Outside diameter 602 672 732 802 kW kW kW kW/kW 609 197 222 3 660 206 243 3 714 243 272 3 778 241 297 2.62 kg kg kg 5285 5484 5645 5833 Plate heat exchanger 6145 6555 - 6315 6745 - l l l kPa 5.5 5.5 5.5 5.5 5.5 5.7 1000 1000 Cylindrical male gas thread 2 2 60.3 60.3 7.5 7.5 5.5 1000 7.5 7.5 7.5 1000 2 60.3 2 60.3 in mm * Nominal conditions: Evaporator entering and l