AHI Carrier Catalog | Page 136

Option 49 Partial Heat recovery

Preliminary performance 30RBM / RBP Cooling only
Condition OAT : 35 ° C - Water : 12-7 ° C
30 RBM 160 180 200 220 260 300 330 360 400 430 470 520
COOLING
THR ( kW )
kW
220.7
237.2
261.2
292.7
346.9
399.5
446.1
487.9
535.2
574.8
617.6
698.0
Heat cap . ( 45-55 ° C )
kW
51.3
55.2
66.9
74.5
102.1
103.1
122.5
124.9
144.6
145.5
168.2
195.3
% reclaim
%
23 %
23 %
26 %
25 %
29 %
26 %
27 %
26 %
27 %
25 %
27 %
28 %
Water flow
/ s
1.2
1.3
1.6
1.8
2.4
2.5
3.0
3.0
3.5
3.6
4.0
4.7
WPD
kPa
5
5
8
9
17
9
13
8
11
12
15
20
Heat cap . ( 50-60 ° C )
kW
42.4
41.5
51.2
58.3
77.6
82.8
97.1
99.1
114.7
115.5
133.5
155.0
% reclaim
%
19 %
17 %
20 %
20 %
22 %
21 %
22 %
20 %
21 %
20 %
22 %
22 %
Water flow
/ s
1.0
1.0
1.2
1.4
1.9
2.0
2.3
2.4
2.7
2.9
3.2
3.7
WPD
kPa
3
3
5
6
10
6
8
5
7
8
10
13
Heat cap . ( 55-65 ° C )
kW
33.9
35.5
41.7
47.9
70.1
68.6
81.4
82.5
95.4
97.2
111.1
128.9
% reclaim
%
15 %
15 %
16 %
16 %
20 %
17 %
18 %
17 %
18 %
17 %
18 %
18 %
Water flow
/ s
0.8
0.8
1.0
1.1
1.7
1.6
2.0
2.0
2.3
2.4
2.7
3.1
WPD
kPa
2
2
3
4
8
4
6
4
5
5
7
9
136 C A R R I E R 2 0 1 6 / 2 0 1 7