AIR-COOLED SCROLL CHILLERS WITH
GREENSPEED INTELLIGENCE 30RBM/30RBP 160-520
®
Electrical data
30RBM
160 180 200 220 260 300 330 360 400 430 470 520
Power circuit
Nominal power supply
Voltage range
Control circuit supply
Nominal unit current draw*
Circuits A + B
Maximum unit power input**
Circuits A + B
Cosine phi, unit at max. capacity**
Maximum unit current draw (Un-10%)***
Circuits A + B
Maximum unit current draw (Un)****
Circuits A + B
Maximum start-up current, standard unit (Un)†
Circuits A + B
Max. start-up current, unit with soft starter (Un)†
Circuits A + B
A
100
110
124
133
161
180
201
221
242
261
282
322
kW
80
0.88
87
0.87
98
0.87
107
0.88
129
0.88
145
0.88
161
0.88
177
0.88
193
0.88
209
0.88
225
0.88
258
0.88
A
144
158
176
192
230
259
288
317
345
374
403
460
A
133
146
163
177
212
239
266
292
319
345
372
425
A
307
356
374
352
423
450
476
503
529
556
583
636
A
261
283
300
305
349
376
403
429
456
482
509
562
COOLING
V-ph-Hz 400 - 3 - 50
V
360 - 440
24 V via internal transformer
*
**
Standardised Eurovent conditions: Evaporator entering/leaving water temperature 12 °C/7 °C, outside air temperature 35 °C.
Power input, compressors and fans, at the unit operating limits (saturated suction temperature 15 °C, saturated condensing temperature 68.3 °C) and nominal voltage of 400 V (data
given on the unit nameplate).
*** Maximum unit operating current at maximum unit power input and 360 V.
**** Maximum unit operating current at maximum unit power input and 400 V (values given on the unit nameplate).
†
Maximum instantaneous start-up current at operating limit values (maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor).
30RBP
160 180 200 220 260 300 330 360 400 430 470 520
Power circuit
Nominal power supply
Voltage range
Control circuit supply
Nominal unit current draw*
Circuits A + B
Maximum unit power input**
Circuits A + B
Cosine phi, unit at max. capacity**
Maximum unit current draw (Un-10%)***
Circuits A + B
Maximum unit current draw (Un)****
Circuits A + B
Maximum start-up current, standard unit (Un)†
Circuits A + B
Max. start-up current, unit with soft starter (Un)†
Circuits A + B
V-ph-Hz 400 - 3 - 50
V
360 - 440
24 V via internal transformer
A
97
107
121
130
158
176
197
216
237
255
276
316
kW
80
0.88
87
0.88
98
0.88
106
0.88
128
0.88
144
0.88
160
0.88
176
0.88
192
0.88
208
0.88
224
0.88
256
0.88
A
142
154
173
189
227
255
284
312
340
369
397
454
A
131
142
160
174
209
235
262
287
314
340
366
419
A
305
353
371
349
420
446
472
498
525
550
577
629
A
259
279
297
302
346
372
399
424
451
477
503
556
*
**
Standardised Eurovent conditions: Evaporator entering/leaving water temperature 12 °C/7 °C, outside air temperature 35 °C.
Power input, compressors and fans, at the unit operating limits (saturated suction temperature 15 °C, saturated condensing temperature 68.3 °C) and nominal voltage of 400 V (data
given on the unit nameplate).
*** Maximum unit operating current at maximum unit power input and 360 V.
**** Maximum unit operating current at maximum unit power input and 400 V (values given on the unit nameplate).
†
Maximum instantaneous start-up current at operating limit values (maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor).
Fan motor electrical data upstream variable frequency drive: Units at Eurovent equivalent conditions and motor ambient air temperature of 50 °C at 400 V: 3.0 A, start-up current 20 A,
power input 1.75 kW.
CONTROLS
HEATING HEATING
Fan motor electrical data: Units at Eurovent equivalent conditions and motor ambient air temperature of 50 °C at 400 V: 3.8 A, start-up current 20 A, power input 1.75 kW.