Physical data
30RBP 160 180 200 220 260 300 330 360 400 430 470 520
COOLING
Fans - Standard unit
Axial Flying Bird 4 with rotating shroud Quantity 3 4 4 4 4 5 5 6 6 7 7 8 Maximum total air flow l / s 13542 18056 18056 18056 18056 22569 22569 27083 27083 31597 31597 36111 Maximum rotation speed tr / s 16 16 16 16 16 16 16 16 16 16 16 16 Evaporator
Twin-circuit plate heat exchanger
Water content |
l |
15 |
15 |
15 |
15 |
19 |
27 |
35 |
33 |
42 |
44 |
47 |
53 |
Max . water-side operating pressure without hydronic module |
kPa |
3200 |
3200 |
3200 |
3200 |
3200 |
3200 |
3200 |
3200 |
3200 |
3200 |
3200 |
3200 |
Hydronic Module ( option ) |
Pump , Victaulic screen filter , safety valve , water valve and air purge , pressure sensors , expansion tank ( option ) |
Pump Centrifugal , monocell , 48.3 r / s , low or high pressure ( as required ), single or dual pump ( as required )
Expansion tank volume |
l |
50 |
50 |
50 |
50 |
50 |
80 |
80 |
80 |
80 |
80 |
80 |
80 |
Max . water-side operating pressure with hydronic module |
kPa |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
Water connections with or |
Victaulic type |
without hydronic module |
|
|
|
|
|
|
|
|
|
|
|
|
|
Diameter |
inch |
3 |
3 |
3 |
3 |
3 |
4 |
4 |
4 |
4 |
4 |
4 |
4 |
Outside tube diameter |
mm |
88.9 |
88.9 |
88.9 |
88.9 |
88.9 |
114.3 |
114.3 |
114.3 |
114.3 |
114.3 |
114.3 |
114.3 |
Chassis paint colour |
Colour code RAL 7035 |
† Eurovent-certified performances in accordance with standard EN14511-3:2013 . Cooling mode conditions : Evaporator water entering / leaving temperature 12 ° C / 7 ° C , outside air temperature 35 ° C . Evaporator fouling factor 0.00 m 2 . k / W
†† Gross performances , not in accordance with EN14511-3:2013 . These performances do not take into account the correction for the proportional heating capacity and power input generated by the water pump to overcome the internal pressure drop in the heat exchanger . Evaporator water entering / leaving temperature 12 ° C / 7 ° C , outside air temperature 35 ° C . evaporator fouling factor 0.00 m 2 . k / W * Options : 15 = Low noise level , 15LS = Very low noise level , 116S = High Pressure dual-pump hydronic module ** Weights are guidelines only . Refer to the unit nameplate . *** In dB ref = 10 -12 W , ( A ) weighting . Declared dualnumber noise emission values in accordance with ISO 4871 ( with an associated uncertainty of +/ -3 dB ( A )). Measured in accordance with
ISO 9614-1 and certified by Eurovent . **** In dB ref 20 µ Pa , ( A ) weighting . Declared dualnumber noise emission values in accordance with ISO 4871 ( with an associated uncertainty of +/ -3 dB ( A )). For information , calculated from the sound power level Lw ( A ).
Eurovent certified data
132 C A R R I E R 2 0 1 6 / 2 0 1 7