AHI Carrier Catalog | Page 131

AIR-COOLED SCROLL CHILLERS WITH GREENSPEED INTELLIGENCE 30RBM/30RBP 160-520 ® Physical data 30RBP 160 180 200 220 260 300 330 360 400 430 470 520 Cooling Nominal cooling capacity kW 168 180 197 216 261 300 331 365 397 430 464 523 ESEER kW/kW 4.18 4.21 4.14 4.18 4.15 4.37 4.28 4.37 4.26 4.36 4.44 4.30 EER kW/kW Eurovent class cooling 3.04 3.12 2.98 2.97 2.90 2.97 2.92 2.95 2.90 2.94 2.90 2.90 B A B B B B B B B B B B Air conditioning application††- standard unit Nominal cooling capacity kW 168 181 198 216 262 301 331 366 398 431 465 524 ESEER kW/kW 4.31 4.36 4.29 4.37 4.32 4.53 4.41 4.53 4.39 4.50 4.60 4.48 EER kW/kW 3.07 3.16 3.03 3.01 2.93 3.00 2.94 2.98 2.93 2.97 2.93 2.93 IPLV kW/kW 4.76 4.85 4.73 4.85 4.75 5.00 4.83 5.00 4.81 4.92 5.00 4.84 Sound power level*** dB(A) 91 92 92 92 92 93 93 93 93 94 94 94 Sound pressure level at 10 m**** dB(A) 59 60 60 60 60 60 60 61 61 62 62 62 COOLING Air conditioning application as per EN14511-3:2013† - standard unit Sound levels Standard unit dB(A) 89 90 90 90 90 91 91 92 92 93 93 93 dB(A) 57 58 58 58 58 59 59 60 60 61 61 61 Standard unit + option 15LS* Sound power level*** dB(A) 85 85 85 86 86 86 86 87 87 88 88 88 Sound pressure level at 10 m**** dB(A) 53 53 53 54 54 54 54 55 55 55 55 56 mm 2410 Dimensions - standard unit Length 3604 4797 Width mm 2253 2253 2253 Height mm 2297 2297 2297 Operating Weight ** Standard unit kg 1252 1293 1293 1423 1445 1901 1937 2105 2162 2603 2621 2827 Standard unit + option 15* kg 1334 1376 1376 1531 1553 2027 2063 2249 2306 2765 2783 3007 Standard unit + option 15 + option 116S* kg 1473 1515 1516 1670 1707 2187 2267 2452 2509 3007 3024 3287 2 2 2 2 3 3 3 3 4 Compressors Hermetic scroll 48.3 tr/s Circuit A 1 1 1 Circuit B 2 2 2 2 2 3 3 3 3 4 4 4 No. of control stages 3 3 3 4 4 5 5 6 6 7 7 8 Refrigerant** - Standard unit R410A 26.75 Circuit A Circuit B kg 8.40 10.90 10.90 12.60 13.10 14.70 15.40 20.30 21.10 23.50 23.50 teqCO2 17.5 22.8 22.8 26.3 27.4 30.7 32.2 42.4 44.1 49.1 49.1 55.9 kg 12.25 12.60 12.60 12.70 13.10 20.20 20.20 20.40 22.20 26.70 26.80 26.95 teqCO2 25.6 26.3 26.3 26.5 27.4 42.2 42.2 42.6 46.4 55.7 56.0 56.3 25 25 20 20 17 17 14 14 13 Capacity control Pro-Dialog+ Control Minimum capacity % 33 Condensers 33 33 Eurovent certified data A R R I E R 2 0 1 6 / 2 0 1 7 131 CONTROLS All-aluminium micro-channel heat exchanger (MCHE) † Eurovent-certified performances in accordance with standard EN14511-3:2013. Cooling mode conditions: Evaporator water entering/leaving temperature 12 °C/7 °C, outside air temperature 35 °C. Evaporator fouling factor 0.00 m2. k/W †† Gross performances, not in accordance with EN14511-3:2013. These performances do not take into account the correction for the proportional heating capacity and power input generated by the water pump to overcome the internal pressure drop in the heat exchanger. Evaporator water entering/leaving temperature 12 °C/7 °C, outside air temperature 35 °C. evaporator fouling factor 0.00 m2. k/W * Options: 15 = Low noise level, 15LS = Very low noise level, 116S = High Pressure dual-pump hydronic module ** Weights are guidelines only. Refer to the unit nameplate. *** In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3 dB(A)). Measured in accordance with ISO 9614-1 and certified by Eurovent. **** In dB ref 20 µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3 dB(A)). For information, calculated from the sound power level Lw(A). C AIR TREATMENT Sound power level*** Sound pressure level at 10 m**** HEATING HEATING Standard unit + option 15*