DUCTABLE AIR-COOLED LIQUID CHILLERS  30RBSY 039-160 Air pressure drop The 30RBSY ranges are designed for indoor installation in a plant room. For this type of installation the cold or hot air leaving the air-cooled air heat exchangers is discharged by the fans to the outside of the building, using a duct system. The units are equipped with fans with available pressure, designed to operate with air discharge ducts with maximum pressure drops of 180 Pa or 240 Pa on certain sizes. Selection based on the ­pressure drop The cooling and heating capacities are given for an available pressure of 160 Pa and for a unit without filter. To calculate the performances at other pressure drops please use the correction factors below. Cooling mode In the cooling mode, the full-load or part-load speed is controlled by a patented algorithm that permanently optimises the condensing temperature to ensure the best unit energy efficiency (EER) whatever the operating conditions and pressure drops of the system ductwork. In the heating mode, the full-load or part-load speed of each circuit is fixed and at the configured maximum (range configurable from 12 r/s to 19 r/s) based on the constraints and characteristics of the installation site. The maximum configured speed applies to both the heating and cooling mode. Duct pressure drop Fan speed, r/s Power input coefficient Cooling ­capacity coefficient 0 50 100 130 160 200 240 12.00 13.33 14.66 15.46 16.26 17.31 18.36 0.943 0.962 0.980 0.990 1.000 1.012 1.023 1.019 1.012 1.006 1.003 1.000 0.998 0.996 30RBSY 070-080/30RBSY 140-160 Duct pressure drop Fan speed, r/s Power input coefficient Cooling c ­ apacity coefficient 0 50 100 130 160 180 15.83 16.81 17.78 18.36 18.36 18.36 0.929 0.944 0.964 0.978 1.000 1.019 1.018 1.016 1.014 1.011 1.000 0.991 CONTROLS AIR TREATMENT Each refrigerant circuit (A and B) must have a separate ducting system to prevent any air recycling between the air heat exchangers of the different refrigerant circuits. 30RBSY 039-060/30RBSY 090-120 HEATING HEATING To compensate for these pressure drops this range of ductable units equipped with variable-speed fans with a maximum speed of 19 r/s. COOLING Selection of a ductable unit C A R R I E R 2 0 1 6 / 2 0 1 7 119