DUCTABLE AIR-COOLED LIQUID CHILLERS
30RBSY 039-160
Physical data
30RBSY
039
045
050
060
070
080
090
100
120
140
160
Outside diameter
mm
60.3
60.3
Colour code: RAL7035
Chassis paint colour
60.3
60.3
60.3
60.3
60.3
60.3
60.3
60.3
HEATING HEATING
AIR TREATMENT
Air conditioning application as per EN14511-3:2013† - standard unit
Condition 1:
Nominal cooling capacity
kW
39.6
44.0
51.2
58.1
66.2
77.7
86.7
97.1
114.4
132.8
153.4
ESEER
kW/ kW
3.81
3.95
3.94
3.85
3.68
3.68
3.82
3.87
3.83
3.74
3.88
EER
kW/ kW
2.87
2.76
2.65
2.67
2.65
2.61
2.69
2.70
2.65
2.63
2.56
Eurovent class cooling
A
B
B
B
B
B
B
B
B
B
B
Condition 2:
Nominal cooling capacity
kW
53.0
58.9
68.5
80.8
83.6
97.0
114.3
126.5
150.8
168.9
191.7
EER
kW/ kW
3.44
3.33
3.11
3.32
2.89
2.96
3.13
3.06
3.09
2.91
2.91
Air conditioning application†† - standard unit
Condition 1:
Nominal cooling capacity
kW
39.9
44.4
51.6
58.6
66.8
78.4
87.2
97.7
115.1
133.6
154.4
ESEER
kW/ kW
3.28
3.46
3.56
3.54
3.31
3.39
3.26
3.35
3.41
3.40
3.61
2.58
2.56
2.52
2.48
EER
kW/ kW
2.69
2.63
2.56
2.59
2.55
2.54
2.55
Condition 2:
Nominal cooling capacity
kW
53.5
59.4
69.3
81.7
84.3
97.9
115.3
127.4
152.1
170.3
193.4
EER
kW/ kW
3.31
3.23
3.06
3.29
2.82
2.92
3.02
2.97
3.03
2.83
2.86
Sound levels
Standard unit - for 160 Pa external static pressure
Sound power level at discharge*
dB(A)
84
84
84
84
87
87
87
87
87
90
90
Sound power level radiated*
dB(A)
84
84
84
84
87
87
87
87
87
90
90
Sound pressure level at 10 m**
dB(A)
53
53
53
53
55
55
56
56
56
58
58
Dimensions
If two values are shown the first one is for standard units and the second one for units with option 23B
Length
mm
2142/ 2142/ 2142/ 2142/ 2142/ 2142/ 2273
2273
2273
2273
2273
2307
2307
2307
2307
2307
2307
Width
mm
1132/ 1132/ 1132/ 1132/ 1132/ 1132/ 2122
2122
2122
2122
2122
1297
1297
1297
1297
1297
1297
Height
mm
1371
1371
1371
1371
1371
1371
1371
1371
1371
1371
1371
Operating weight with MCHE coil***
771
780
793
901
932
Standard unit without hydronic module
kg
436
443
449
464
461
480
Standard unit with hydronic module
Single high-pressure pump
kg
466
473
479
494
491
510
803
812
829
940
971
Dual high-pressure pump
kg
491
499
504
520
517
536
848
857
877
977
1008
Compressors
Hermetic scroll compressors, 48.3 r/s
Circuit A
2
2
2
2
2
2
3
3
3
2
2
Circuit B
2
2
No of control stages
2
2
2
2
2
2
3
3
3
4
4
Refrigerant charge with MCHE coil***
R-410A
C ircuit A
kg
4.7
4.5
6.3
6.7
6.2
7.3
9.5
10.8
11.4
6.3
8
Circuit B
kg
6.3
8
Capacity control
Touch Pilot Junior
Minimum capacity
%
50
50
50
50
50
50
33
33
33
25
25
Condensers
All-aluminium microchannel heat exchanger (MCHE)
Fans
Axial Flying Bird IV with rotating shroud
Quantity
1
1
1
1
1
1
2
2
2
2
2
3908
4982
5267
6940
6936
7370
9958
10534
Maximum total air flow
l/s
3885
3883
3687
Maximum rotation speed
r/s
16
16
16
18
18
18
16
16
16
16
16
Evaporator
Direct expansion. plate heat exchanger
Water volume
l
2.6
3.0
3.3
4.0
4.8
5.6
8.7
9.9
11.3
12.4
14.7
Without hydronic module (option)
Max. water-side operating pressure
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
without hydronic module
With hydronic module (option)
Single or dual pump (as selected)
Pump, Victaulic screen filter, safety valve, expansion tank, purge valves (water + air), pressure sensors
Expansion tank volume
l
12
12
12
12
12
12
35
35
35
35
35
Expansion tank pressure****
bar
1
1
1
1
1
1
1.5
1.5
1.5
1.5
1.5
Max. water-side operating pressure
kPa
400
400
400
400
400
400
400
400
400
400
400
Water connections with/without hydronic module Victaulic
Diameter
in
2
2
2
2
2
2
2
2
2
2
2
COOLING
Cooling
60.3
† Eurovent-certified performances in accordance with standard EN14511-3:2013.
†† Gross performances, not in accordance with EN14511-3:2013. These performances do not take into account the correction for the proportionnal heating capacity and power input
generated by the water pump to overcome the internal pressure drop in the heat exchanger.
Condition 1: cooling mode conditions: evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C, evaporator fooling factor 0 m².K/W
Condition 2: cooling mode conditions: evaporator water entering/leaving temperature 23°C/18°C, outside air temperature 35°C, evaporator fooling factor 0 m².K/W
* In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with
ISO 9614-1 and certified by Eurovent.
** In dB ref 20μPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated from
the sound power level Lw(A).
*** Weight shown is a guideline only. Please refer to the unit nameplate.
**** When delivered, the standard pre-inflation of the tank is not necessarily the optimal value for the system. To permit changing the water volume, change the inflation pressure to a
pressure that is close to the static head of the system. Fill the system with water (purging the air) to a pressure value that is 10 to 20 kPa higher than the pressure in the tank
Eurovent certified data
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
109