Electrical heater (option)
Electric heater assembly in 1 stage. For 2 stages, it is necessary to check if it is possible and the price.
Important: with this option, the air fl ow controller is included.
Avalaible capacities
40HB/HF
Power supply
400 V / III ph / 50 Hz
Power output
kW
3
6
9
12
15
18
80 / 90
Current
A
4,3
8,7
13
17,3
-
-
120 / 160
Current
A
4,3
8,7
13
17,3
21,7
26
Frame for assembly of the electrical heater on fan supply
40HB/HF
80 / 90
120
160
Power output (kW)
Dimensions (mm)
A
B
C
3 a 6 kW (1 row)
150
432
341
9 a 12 kW (2 rows)
262
432
341
3 a 6 kW (1 row)
150
432
341
9 a 12 kW (2 rows)
262
432
341
12 a 18 kW (2 rows)
262
482
443
3 a 12 kW (1 row)
150
547
443
15 a 18 kW (2 rows)
262
547
443
Note: This frame is designed with side access for maintenance purposes.
Auxiliary Hot Water Coil (Optional)
Two-row hot water coils for mounting in duct
40HB/HF
AIR TREATMENT
Nominal air flow
m3/h
Air pressure drop
Water 80/60ºC
Water 90/70ºC
Weight (empty)
90
120
160
4.000
4.600
6.000
7.000
mm.w.c
3,6
4,5
3,4
4,4
Heating capacity
kW
34,7
37,7
52,7
57,9
Water flow
m3/h
1,5
1,6
2,3
2,5
Water pressure drop
m.w.c
1,0
1,2
1,2
1,4
Heating capacity
kW
42,8
46,6
65,0
71,4
Water flow
m3/h
1,8
2,0
2,8
3,1
Water pressure drop
m.w.c
1,5
1,7
1,8
2,1
kg
9,5
9,5
13,5
13,5
1 1/4”
1 1/4”
1 1/2”
1 1/2”
Diameter of hydraulic connections
792
80
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7