AHI Carrier Catalog | Page 768

Power level and sound pressure level dB(A) A) The sound power level in the outdoor fan to be taken into account for the silencer calculation: 50HB/HF 55 65 80 90 120 160 dB(A) 80,5 82,7 74,4 76,3 83,5 83,3 B) The sound power level in the indoor fan to be taken into account for the silencer calculation: 50HB/HF 55 65 80 90 120 160 dB(A) 72.0 77.4 80.4 77,1 79,2 77,1 C) The sound pressure level of the unit, with the return and supply connections ducted, measured at a distance of 5 meters, in open field, the directivity at 2 and 1.5 meters from the earth is: 50HB/HF 55 65 80 90 120 160 dB(A) 69.3 71.6 69.4 70.8 70.7 71.2 Note: The sound pressure level depends on the installation conditions and, as such, it only indicated as a guide. AIR TREATMENT Unit configuration ■■ Casing -- Casing made of galvanised steel metal with polyester paint, colour RAL 7035, dried in oven and thermally isolated -- Self-supporting frame and and fan access panels, cooling circuit and electric panel ■■ Outdoor circuit -- Centrifugal fan with coupling by pulleys and belts -- Anti-bird grid, in aspiration -- Condensates drain pan with asphaltic paint Independent drain -- Copper pipe and aluminium fins coil ■■ Indoor circuit -- Centrifugal fan with coupling by pulleys and belts -- Reusable air filter -- Condensate collection pan. Independent drain -- Copper pipe and aluminium fins coil ■■ Cooling circuit -- Scroll compressor, assembled over shock absorbers Thermal protection -- Thermostatic expansion valve with outdoor pressure external equalisation -- Four-way valve for cycle inversion and crankcase heater (in heat pump units) -- Anti-acid dehydrator filter 768 ■■ Protections -- High pressure pressostat -- Low pressure pressostat -- Automatic switch in the control circuit -- Magnetothermic protection switches for the compressor and fan motor power line -- Main door switch -- Fan thermal protection -- Compressor discharge temperature control ■■ Electric panel -- Complete and fully wired electrical panel -- Transformer for power supply without neutral -- Main earth connection -- Compressor and fan motors contactors C A R R I E R 2 0 1 6 / 2 0 1 7