CASSETTE FAN COIL UNITS 42GW
Supply of conditioned air duct to
an adjacent room
Serviceability
■■ All the key components (motors, fans and drain pump) are
accessible from the bottom by simply removing the grille.
These components can be removed without disturbing
the other components or any surrounding ceiling tiles.
■■ This option allows supply of conditioned air to a room
located close to the Idrofan cassette through an air duct
(customer-supplied). If this option is used, the outlet corresponding to the duct must be closed, using the air supply
outlet obstruction kit provided. The kit cannot be used in
units equipped with electric heater. An air inlet grille must be
fitted (if possible near the floor) between the air-conditioned
room (where the unit is situated) and the adjacent room or,
alternatively, the door must be undercut.
■■ The duct lengths can be calculated in accordance with
the “air distribution to an ad jacent room” diagram in the
IOM, also taking into account the pressure drop through
air diffusers and fresh air filters.
Operating limits
Water circuit
Maximum water-side pressure: 1400 kPa (142 m WG)
Indoor temperature
Minimum entering water temperature: 5°C
Maximum entering water temperature: 80°C
Minimum temperature: 5°C
Maximum temperature: 32°C for units with electric heaters
Power supply
Nominal operating limits
230 V - 1 ph - 50 Hz
Min.207 - Max.253 V for units without electric heaters
Min.216 - Max.244 V for units with electric heaters
42GW
Louvres all open
High speed Medium
speed
One louvre closed
Low speed High speed Medium
speed
Two louvres closed
Low speed High speed Medium
speed
Low speed
200/209
3.8
3.2
2.7
4.3
3.7
3.0
4.8
4.1
3.4
300/309
4.0
3.4
2.8
4.5
3.8
3.2
5.0
4.3
3.5
400/409
4.8
4.1
3.4
5.3
4.5
3.7
5.8
4.9
4.1
500/509
3.0
2.6
2.1
3.5
3.0
2.5
4.0
3.4
2.8
600/609
3.4
2.9
2.4
3.9
3.3
2.7
4.4
3.7
3.1
701/709
4.3
3.7
3.0
4.8
4.1
3.4
5.3
4.5
3.7
Notes:
1. The louvres were adjusted to use the Coanda effect to obtain an air flow pattern that adheres as closely as possible and parallel to the ceiling.
2. The air throw is defined as the distance at which air flow speed falls to 0.2 m/s, when the air flow leaves the unit parallel to the ceiling.
3. The values are to be considered as indicative, as they may vary according to the type of ceiling, room dimensions and even the furniture used.
Valve kit
Valve kit
42GW 9029 42GW 9031 42GW 9030 42GW 9032 42GW 9033 42GW 9035 42GW 9034 42GW 9036
Unit option (10th digit) H - 4 ways
H - 4 ways
H - 4 ways
H - 4 ways
G - 2 ways
G - 2 ways
G - 2 ways
G - 2 ways
Description
1" cold
3/4" cold +
1/2" hot
1" cold +
3/4" hot
3/4" cold
1" cold
3/4" cold +
1/2" hot
1" cold +
3/4" hot
3/4" cold
Valve pitch, mm
40
73
40/40
73/40
40
73
40/40
73/40
Valve face
Flat
Flat
Flat
Flat
Flat
Flat
Flat
Flat
AIR TREATMENT
Air throw, m
200C, 300C, 400C
X
-
-
-
X
-
-
-
209C, 309C, 409C
X
-
-
-
X
-
-
-
500C, 600C, 701C
-
X
-
-
-
X
-
-
509C, 609C, 709C
-
X
-
-
-
X
-
-
CONTROLS
2 pipes
4 pipes
200D, 300D, 400D
-
-
X
-
-
-
X
-
209D, 309D, 409D
-
-
X
-
-
-
X
-
600D, 701D
-
-
-
X
-
-
-
X
609D, 709D
-
-
-
X
-
-
-
X
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7