AIR-TO-WATER HEAT PUMPS 30RQV 017-021
Physical data
30RQV
17
21
14,9
3,0
18,6
3,1
B
20,2
3,8
A
4,01
A
25,8
3,8
A
3,85
17,1
4,1
A
16,9
3,3
A
21,1
4,1
A
20,0
3,3
A
Cooling
Standard unit
Full load performances*
C1
C1
Nominal capacity
EER
C1
C2
C2
C2
Eurovent class cooling
Nominal capacity
EER
Eurovent class cooling
ESEER
Seasonal efficiency
kW
kW/kW
kW
kW/kW
kW/kW
Nominal capacity
COP
Eurovent class heating
Nominal capacity
COP
Eurovent class heating
kW
kW/kW
H3
H3
H3
H3
H3
H3
H3
Nominal capacity
COP
SCOP
Ƞs heat
Prated
Annual Energy consumption
Energy class
kW
kW/kW
kW/kW
%
kW
KWh
15,2
2,7
3,1
121
9,5
6269
A+
21,1
2,5
2,9
113
15,43
10980
A+
dB(A)
dB(A)
71
40
74
43
mm
mm
mm
1109
584
1579
1109
584
1579
kg
Rotary compressor
R410A
kg
190,9
1
199,4
1
8
8
Sound levels
Standard unit
Sound power level (2)
Sound pressure level at 10 m (3)
Dimensions - Standard unit
Length (5)
Width
Height
Operating Weight (1)
Standard unit
Compressors
Refrigerant
Charge (1)
Capacity control
Minimum capacity (6)
Air heat exchanger
Fans - Standard unit
Quantity
Maximum total air flow
Maximum rotational speed
kW
kW/kW
%
33%
Grooved copper tubes, aluminium fins
Axial type fan
2
l/s
2000
rps
14
41%
2
2400
16
Water heat exchanger
Water volume
Max water-side operating pressure without hydronic module
Hydronic module (option)
Brazed plate heat exchanger
l
1,52
1,9
kPa
1000
1000
Pump, relief valve, paddle flow switch, expansion tank (option)
Pump
Expansion tank volume
Max. water-side operating pressure with hydronic module (4)
Water connections (Without Hydronic Module)
Inlet diameter (BSP GAS)
Outlet diameter (BSP GAS)
Water connections (With Hydronic Module)
Inlet diameter (BSP GAS)
Outlet diameter (BSP GAS)
Water Filling System (Option 287)
Diameter (BSP GAS)
Chassis paint colour
Centrifugal pump (fixed speed or variable speed)
l
8
8
kPa
300
300
inch
inch
1
1
1
1
inch
inch
1-1/4
1
1-1/4
1
inch
Colour code:
1/2
RAL 7035
1/2
RAL 7035
AIR TREATMENT
Seasonal efficiency**
H1
H1
H1
H2
H2
H2
*
**
C1
C2
H1
H2
H3
(1)
(2)
In accordance with standard EN 14511-3:2013
In accordance with standard EN 14825:2013, Average climate
Cooling mode conditions : evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C, evaporator fooling factor 0m² K/W
Cooling mode conditions : evaporator water entering/leaving temperature 23°C/18°C, outside air temperature 35°C, evaporator fooling factor 0m² K/W
Heating mode conditions : Water heat exchanger water entering/leaving temperature 30°C/35°C, fooling factor 0m² K/W. Outside air temperature 7°C db / 6°C wb
Heating mode conditions : Water heat exchanger water entering/leaving temperature 40°C/45°C, fooling factor 0m² K/W. Outside air temperature 7°C db / 6°C wb
Heating mode conditions : Water heat exchanger water entering/leaving temperature 47°C/55°C, fooling factor 0m² K/W. Outside air temperature 7°C db / 6°C wb
Values are guidelines only. Refer to the unit nameplate.
In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with
ISO 9614-1 and certified by Eurovent.
(3) In dB ref 20 μPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated from
the sound power level Lw(A).
(4) Min. water-side operating pressure with fixed speed hydronic module is 50 kPa and with variable speed hydronic module is 40 kPa.
(5) Length = 1141 mm if main disconnect switch
(6) Cooling Eurovent condition
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
423
CONTROLS
Standard unit
Full load performances*
HEATING
Heating