AHI Carrier Catalog | Page 241
WATER-COOLED SCREW COMPRESSOR
LIQUID CHILLERS 30HXC 080-375
Physical data
080 090 100 110 120 130 140 155 175 190 200 230 260 285 310 345 375
30HXC
Cooling
C1
Nominal capacity
kW
C1
EER
kW/kW 5.03 4.79 4.82 4.60 4.87 4.72 4.74 4.57 4.68 4.73 4.74 4.74 4.46 4.77 4.76 4.56 4.66
C1
Eurovent Energy Class
ESEER
312
B
kW/kW
B
348
375
B
413
C
450
B
B
510
B
543
C
600
B
652
B
701
B
814
B
899
C
987
B
1109 1207 1302
B
C
B
5.56 5.41 5.31 5.28 5.23 5.21 5.17 4.85 5.03 4.97 5.08 5.06 5.01 5.11 5.49 5.39 5.34
Sound Power Level Standard Unit
dB(A)
94
Operating weight
kg
2274 2279 2302 2343 2615 2617 2702 2712 3083 3179 3873 4602 4656 4776 5477 5553 5721
Depth
mm
2558 2558 2558 2565 3275 3275 3275 3275 3275 3275 3903 3924 3924 3924 4533 4533 4533
Length
mm
980
Height
mm
1800 1800 1800 1850 1816 1816 1816 1816 1940 1940 1980 2060 2060 2060 2112 2112 2112
94
94
94
94
97
98
100
101
101
99
101
102
102
103
104
104
Dimensions, standard unit
980
980
980
980
980
980
980
980
980
1015 1015 1015 1015 1015 1015 1015
Refrigerant
R-134a
Compressors
06N semi-hermetic twin-screw compressor
Quantity - Circuit A
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
Quantity - Circuit B
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
Capacity control
Pro-Dialog Plus control
No. of control steps
6
6
6
6
6
6
6
8
8
8
8
10
10
10
Evaporator
Shell and tube with internally finned copper tubes
5
5
6
6
6
6
8
8
8
6
6
6
8
8
8
8
8
8
Water connections
6
6
6
Victaulic
Inlet/outlet
in
4
4
5
4
5
5
5
5
Condenser
Shell and tube with internally finned copper tubes
Water connections
Victaulic
Inlet/outlet
in
5
5
5
5
5
5
5
5
COOLING
Seasonal
Efficiency*
287
C1 Cooling mode conditions: Evaporator Water heat exchanger, entering/leaving temperature 12°C/7°C, fouling factor 0 m2 K/W. Condenser Water heat exchanger, entering/leaving temperature
30°C/35°C, fouling factor 0 m2 K/W.
* In accordance with standard EN14511-3:2013
Weight shown is a guideline only. The dimensions shown are for the standard unit. For other unit types please refer to the dimensional drawings.
HEATING HEATING
Full loa d
performances*
Electrical data
30HXC
080 090 100 110 120 130 140 155 175 190 200 230 260 285 310 345 375
Power circuit
Nominal power supply (Un)*
V-ph-Hz
Control circuit supply
400-3-50 ± 10%
The control circuit is supplied via the factory-installed transformer
Nominal current drawn*
A
101
115
127
143
149
168
190
207
226
234
255
294
337
354
399
448
477
Maximum starting current***
A
181
206
223
249
267
298
333
355
382
442
841
978
1027
1200
1129
1184
1373
Circuit A**
A
-
-
-
-
-
-
-
-
-
-
712
822
871
1028
844
871
1028
Circuit B**
A
-
-
-
-
-
-
-
-
-
-
605
715
715
856
844
871
1028
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
CONTROLS
* Standard Eurovent conditions: Evaporator entering/leaving water temperature 12°C and 7°C. Condenser entering/leaving water temperature 30°C/35°C.
** Maximum unit operating current at maximum unit power input.
*** Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest compressor).
C
AIR TREATMENT
Eurovent certified data
241