483760 Edition II II | Page 216

217 | Work SHR 11004 Commercial Heat Recovery Ventilators The SHR 11004 Commercial Heat Recovery Ventilation system (HRV) complements today's tight buildings. Fantech Heat Recovery Ventilators (HRV) are designed to supply air into a building while exhausting an equal amount of contaminated air to the outside. The aluminum heat exchange core transfers sensible energy between air steams resulting in tempering of the supply air and reduced loads on the HVAC system. A preset defrost sequence is activated at an outdoor air temperature of 23ºF and lower. During the defrost sequence, the supply blower shuts down & the exhaust blower continues to ventilate for a few minutes. The unit then returns to normal operation, and continues cycle. Airflow up to 1032 cfm @ 0.4” Ps Push-pull configuration External low voltage contacts Dual service doors & reversible electrical box External three position switch (Low/Standby/Medium) Improved BMS integration • • • • • • Maximum continuous airflow in.wg cfm 0.3” Ps 0.4” Ps 0.5” Ps 0.6” Ps 0.7” Ps 0.8” Ps 0.9” Ps 1.0” Ps 1.1” Ps 1.2” Ps 1.3” Ps 1.4” Ps 1.5” Ps 1.6” Ps Supply air flow (high) 1082 1032 982 932 882 832 782 732 682 632 582 532 482 432 Exhaust air flow (high) 1082 1032 982 932 882 832 782 732 682 632 582 532 482 432 Energy performance Supply temperature Net airflow Apparent sensible effectiveness F cfm % 35 1035 63 35 776 68 95 1035 47 95 776 49 Heating O Heating Cooling Specification data Model Voltage / phase V/~ W A cfm SHR 11004 120 / 1 1320 11 1032 fantech Rated power Max amps Average airflow @ 0.4” Ps Connection Defrost cycle Shipping weight Side Auto 310 Item # lbs List price USD 40419 3,478.00