| Wash
183
FRD Series
Inline Mixed Flow Rectangular Fans
Fantech, Inc. certifies that
the models shown herein are
licensed to bear the AMCA
Seal. The ratings are based
on the tests and procedures
performed in accordance with
AMCA Publication 211 and
comply with the requirements
of the AMCA Certified
Ratings Program. Performance
certified is for installation
type D – Ducted inlet, Ducted
outlet. Performance ratings
do not include the effects of
appurtenances (accessories).
The FRD Series centrifugal type exhaust/supply fans are specifically
designed for large ventilation needs where space is at a premium, such
as hospitals, schools, or office buildings. System balancing is easy - a
simple speed adjustment equalizes all vents to compensate for hot or cold
spots.
The compact housing design of the FRD Series allows for installation
directly within rectangular ductwork (ranging from 12”x 6” ducts to 24”x
14” ducts), without the need for large elbows or transitional sections. FRD
Series fans are simple to install; no extra materials are required. Simply
mount the fan at any angle in any point in the ductwork. The motor is
mounted on a hinged door – just swing the door out for easy access to
the motor and wiring connections.
•
•
•
•
•
Hinged door for service access
Airflow up to 2318 cfm
Terminal box with prewired electrical strip
100% speed controllable
Airstream temperatures of up to 140° F
Specification data
Rated
power
Voltage /
phase
RPM
Max.
apms
W
V/~
min-1
A
FRD 12-6
84
120 / 1
2550
FRD 16-8
150
120 / 1
FRD 16-8XL
264
Model
0.0” Ps
.25” Ps
.50” Ps
.75” Ps
0.741
309
262
214
2950
1.301
560
499
120 / 1
2800
2.321
658
599
1
1.0” Ps
1.5” Ps
2.0” Ps
Max Ps
Sones†
Shipping
weight
171
133
75
-
2.01
8.0
434
368
300
191
535
471
406
290
119
2.57
196
3.44
cfm
Item #
List price
17
40030
326.00
13.0
30
40031
450.00
13.1 ‡
30
40032
528.00
43
40033
809.00
86
40115
1,448.00
Shipping
weight
Item #
List price
in.wg
lbs
FRD 20-10
191
120 / 1
1650
1.68
1013
915
814
724
617
225
-
1.84
16.7
FRD 24-14
597
120 / 1
1650
5.182
2318
2149
1939
1752
1527
1090
377
2.16
18.2
Voltage /
phase
RPM
Max.
apms
0.0” Ps
.25” Ps
.50” Ps
.75” Ps
1.0” Ps
1.5” Ps
2.0” Ps
Max Ps
Sones†
Model
Rated
power
W
V/~
min-1
A
cfm
in.wg
‡
USD
lbs
USD
FRD 12-6-230
81
230 / 1
2700
0.35
275
240
210
180
143
83
-
1.6
10.9
17
40449
391.00
FRD 16-8-230
225
230 / 1
3050
0.611
585
535
475
410
345
222
135
2.3
14.7
30
40590
514.00
FRD 16-8XL-230
176
230 / 1
2880
0.91
1
553
518
478
438
416
336
261
2.5
15.6
30
45307
575.00
FRD 20-10-230
198
230 / 1
1680
0.86
1
964
851
730
617
485
166
-
1.5
16.0
43
44002
883.00
FRD 24-14-230
810
230 / 1
1600
3.601
2122
1985
1864
1679
1512
1109
588
2
20.6
86
44003
1,738.00
1
Performance certified is for installation type D - ducted inlet, ducted outlet. Speed (RPM) shown is nominal. Performance is based on actual speed of test. Performance ratings do not include the effects of
appurtenances (accessories).
†
The sound ratings shown are loudness values in fan sones at 5ft. (1.5m) in hemispherical free field ca