483760 Edition II II | Page 134
135 |
Cook
5BDU Series
Belt Drive Upblast Roof Ventilators
To complete our range of Upblast Roof fans, and allow for maximum quick
turn availability, Fantech offers the complete range as 3 easily assembled
components. The fans come with a Shell featuring a fully welded windband,
heavy duty motor supports and machine balanced and mounted blower wheel.
Factory pressed bearings complete the shaft and motor mount assembly.
Fantech, Inc. certifies that the Belt-Drive
Upblast Centrifugal Roof Ventilators
shown herein are licensed to bear
the AMCA Seal. The ratings shown
are based on tests and procedures
performed in accordance with AMCA
Publication 211 and AMCA Publication
311 and comply with the requirements
of the AMCA Certified Ratings Program.
Choosing the right motor is as easy as finding your desired airflow and
matching that performance with the correspon-ding motor size and drive pack.
Not all available motor combinations are shown in the specification data table
below. Please refer to our online PRV selection tool for a complete listing of Fan
combinations and performance data at fanselect.fantech.net
Specification data
Rated
power
Voltage
RPM
HP
V
min-1
1/4
120 / 230
1423
0.0” Ps
0.125” Ps
0.25” Ps
0.375” Ps
0.50” Ps
Model
5BDU 12
1/4
120 / 230
1210
5BDU 13
1/3
1330
1/4
5BDU 15
120 / 230
120/208-230
1033
1/3
120/208-230
1136
1/2
120/208-230
208-230/460
1301
1/3
5BDU 16
120 / 230
960
1/2
120/208-230
208-230/460
1100
3/4
120/208-230
208-230/460
1260
1/3
120 / 230
811
1/2
120/208-230
208-230/460
3/4
5BDU 18
120/208-230
208-230/460
1/3
120 / 230
1/2
120/208-230
208-230/460
928
1062
695
800
5BDU 20
3/4
1
120/208-230
208-230/460
120/208-230
208-230/460
915
1010
0.625” Ps
0.75” Ps
0.875” Ps
1.00” Ps
1.25” Ps
cfm
Sones † | BHP #
1390
1328
1266
1195
1121
1034
939
831
-
-
12.5 | 0.21
12.3 | 0.22
11.7 | 0.23
11.3 | 0.23
10.8 | 0.24
10.2 | 0.24
9.7 | 0.24
9.5 | 0.24
-
-
1730
1638
1543
1443
1334
1216
1061
-
-
-
12.2 | 0.21
11.2 | 0.22
11.5 | 0.23
11.0 | 0.24
10.3 | 0.25
9.4 | 0.25
8.5 | 0.25
-
-
-
1902
1818
1734
1643
1552
1449
1343
1201
-
-
14.1 | 0.28
13.7 | 0.29
13.1 | 0.30
12.9 | 0.31
12.9 | 0.31
12.5 | 0.32
11.1 | 0.33
10.2 | 0.33
-
-
1950
1840
1727
1599
1450
1258
568
-
-
-
11.8 | 0.22
11.5 | 0.23
11.5 | 0.24
10.8 | 0.25
10.5 | 0.25
9.9 | 0.25
8.6 | 0.16
-
-
-
2145
2045
1945
1832
1713
1571
1393
1070
-
-
13.1 | 0.29
12.8 | 0.30
12.5 | 0.31
12.3 | 0.32
12.0 | 0.33
11.4 | 0.33
10.8 | 0.33
10.2 | 0.30
-
-
2456
2369
2282
2193
2091
1989
1868
1745
1572
-
15.4 | 0.44
15.4 | 0.45
15.1 | 0.47
14.9 | 0.48
14.4 | 0.49
14.1 | 0.49
13.8 | 0.50
13.2 | 0.50
12.9 | 0.49
-
2520
2377
2232
2076
1910
1702
1390
-
-
-
12.4 | 0.29
12.1 | 0.30
11.7 | 0.31
10.9 | 0.32
10.6 | 0.33
9.6 | 0.33
8.8 | 0.31
-
-
-
2887
2762
2637
2507
2370
2226
2077
1847
1529
-
15.7 | 0.44
14.7 | 0.45
14.2 | 0.46
13.5 | 0.47
12.8 | 0.48
12.0 | 0.49
11.8 | 0.50
11.4 | 0.49
9.8 | 0.47
-
3307
3198
3098
2980
2864
2744
2623
2492
2360
-
18.2 | 0.66
17.7 | 0.68
17.4 | 0.69
17.2 | 0.70
16.2 | 0.71
15.7 | 0.72
15.3 | 0.74
14.9 | 0.74
14.2 | 0.75
-
2765
2600
2419
2217
1987
1676
-
-
-
-
10.1 | 0.27
9.8 | 0.29
9.6 | 0.30
9.2 | 0.30
8.6 | 0.30
8.4 | 0.31
-
-
-
-
3164
3020
2873
2701
2523
2321
2070
1589
-
-
11.7 | 0.41
11.5 | 0.43
11.6 | 0.44
11.2 | 0.46
10.5 | 0.47
10.1 | 0.47
9.8 | 0.47
9.0 | 0.43
-
-
3621
3496
3368
3233
3080
2926
2753
2577
2335
-
14.8 | 0.61
14.5 | 0.63
14.3 | 0.65
14.1 | 0.67
13.9 | 0.69
13.3 | 0.69
12.8 | 0.70
12.6 | 0.70
11.9 | 0.70
-
3329
2996
2742
2456
2094
-
-
-
-
-
12.9 | 0.29
12.2 | 0.30
11.8 | 0.32
11.4 | 0.33
11.2 | 0.32
-
-
-
-
-
3718
3515
3304
3078
2820
2527
2005
-
-
-
14.0 | 0.44
13.6 | 0.46
13.1 | 0.48
12.6 | 0.49
12.2 | 0.50
12.3 | 0.50
12.0 | 0.47
-
-
-
4252
4075
3898
3703
3505
3282
3039
2734
2175
-
15.7 | 0.65
15.3 | 0.68
15.1 | 0.70
14.5 | 0.72
14.3 | 0.74
13.7 | 0.75
13.9 | 0.75
13.4 | 0.74
12.8 | 0.68
-
4693
4533
4373
4206
4026
3846
3643
3423
3181
1422
17.6 | 0.88
17.2 | 0.91
17.1 | 0.93
16.6 | 0.96
16.2 | 0.96
16.2 | 0.96
15.5 | 1.00
14.9 | 1.00
14.9 | 1.00
14.8 | 0.63
Performance certified for installation type A: free inlet, free outlet. Performance rating includes the effect of bird screen. # Power rating (BHP) does not include transmission losses.
†
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA standard 301. Values shown are for installation type A, free inlet hemispherical sone levels.